1000L/H R.O. Water Purification System
Product Details
Design basis and treated water standard:
1. Design Basis
1.1 Produced water’s application: Pure drinking water
1.2 The capacity of produced water: 1000L /H
1.3 System Configuration: Pretreatment + One Stage Reverse Osmosis Desalination System.
1.4 Designed recovery: 50-65%.
1.5 Rejection rate:≥ 97%
1.6 Voltage: 3 phases, 380V, 50Hz; Power: 2.8KW (Can be customized at your country’s voltage, please tell us about it when ordering)
Technical Process:
Water Source → Raw Water Tank → Booster Pump → Sand Filter
R.O.System ← High pressure pump ← Security (Softener) ← Carbon Filter
Pure Water Tank
↑ Ozone Generator
↑ UV sterilizer
Main Components List:
Basic Configuration | Item | Description |
Pretreatment part | Feed pump | CNP CDL2-50 |
Sand filter | Dia 400*1600 (filter 230kg) SUS304/FPR | |
Active Carbon filter | Dia 400*1600 (filter 85kg) SUS304/FPR | |
Micron filter | 20″ X 5 micron filter | |
RO Part | Pressure pump | CNP CDL2-180 |
RO membrane | FILMTEC BW30-4040 x 3pcs | |
Membrane vessel | 4040 stainless steel VESSEL 3 SETS | |
Indicators | Conductivity, pump operation | |
Piping and controlling valve | Piping and valves | U-PVC/ SS304 |
Control system & Indicator | Water level control, Pump protecting, Automatic electric valve control | |
Other fittings of machine | Pressure gage | 4 sets |
Conductivity table | CM230 X 2sets | |
Main frame | Stainless steel 1set | |
solenoid valve | DN20 1set | |
Pipeline flow meter | 10GMP 2sets |